Conex DIA-G

Gas warning unit for chlorine, chlorine dioxide, ozone, ammonia and hydrochloric acid
Optimum safety - minimum labour input: The Conex DIA-G safety system monitors the concentration of the gases chlorine, chlorine dioxide, ozone, ammonia and hydrochloric acid in the air of storage rooms. It is equipped with a range of functions providing the users with optimum safety combined with minimum labour input. One unit can use two interconnected sensors to monitor two different gases, two different gas concentrations or two different gas storage rooms in parallel.

Applications:
  Drinking water
  Swimming pool water
  Industrial water
  Waste water

Amplifier Conex DIA-G
 Electronics  16 bit microprocessor
 Relay outputs  5 potential-free relay outputs per software switchable to
 N.O. or N.C. (fail-safe), max. 250 V/6 A, max. 550 VA
 - 2 relays for the limit values of every of the two sensors
 - 1 alarm relay
 Power supply  110 - 240 V (50/60 Hz) or 24 V DC
 Separate
 Sensor Interface
 for one potentiostatic sensor, directly plugged into
 the Interface.

Gas sensors
 Gases   Measuring
 range
 Accuracy   Response time
 (20 °C) 
 max. distance
 from the amplifier 
Amperometric sensors
 Cl2
 ClO2
 O3
 0 - 5 ppm  +/-10 %  2 s  100 m
Potentiostatic sensors
 Cl2  0.00 – 20.00 ppm  < 0.05 ppm  < 30 s  500 m
 ClO2  0.00 – 1.00 ppm   < 0.03 ppm  < 120 s
 O3   0.00 – 1.00 ppm  < 0.02 ppm  < 60 s
 NH3  0 – 100 ppm  < 1 ppm  < 120 s
 HCl  0.00 – 30.0 ppm  < 0.07 ppm  < 70 s

Features & Benefits:
  Optimum safety: Thanks to permanent sensor monitoring, the alarm relay and the possibility of backup operation (uninterrupted current supply) by connection of an external buffer battery
  Very short response time in case of a sudden change of the gas concentration
  Long service life of the sensor element - without necessity of maintenance
  Sensor recognition and auto-calibration, monitoring of the lifetime of the sensor
  Internal CAN bus interface for the connection of potentiostatic sensors using Bus lines with a total length of max. 500 m
  External CAN bus interface for the connection of Conex DIA-G to the visualising software AquaVision 2 or to PLC
 
enlarge Image
Conex® DIA-G with two amperometric sensors



enlarge Image
Conex® DIA-G with one amperometric sensor and one potentiostatic sensor (plugged into a Sensor interface)




enlarge Image
Conex® DIA-G with two potentiostatic sensors (plugged into two Sensor interfaces)





More questions?
With pleasure we give answers to your questions and send you more detailed information leaflets. » To contact form